4 function chart – VEGA VEGAKON 66 with transistor output User Manual

Page 18

Advertising
background image

The instrument is adapted to the medium, i.e. the transistor
blocks when max. level is reached. Only when decreasing the
min. probe, the transistor conducts again.

Example: A filling pump is switched on when the min. signal is
decreased, fills the vessels until max. signal is reached and is
then switched off.

The following settings apply to products with low conductivity
(<3 mS)

1

Empty the vessel until the min. measuring electrode is only
covered approx. 1 cm

2

Switch on voltage supply

3

Set the A/B switch to mode B

4

Set the rotary switch to position "TEST max."

5

Turn the rotary switch slowly anticlockwise until the red
LED lights

The instrument is adapted to the medium, i.e. the transistor
conducts at max. level. Only when decreasing the min. probe,
the transistor blocks again.

Example: An emptying pump is switched on when the max.
signal is reached, empties the vessels until min. signal is
reached and is then switched off.

In case of several measurement loops (same medium), the
adjustment of one instrument with medium is sufficient. The
determined switch position can be transferred to all other
instruments.

When the conductivity value is known, the switching point
adjustment can be carried out according to the setup in chart
"R

otary switch adjustment".

When exchanging the electronics module, it is sufficient to take
over the setting of the old electronics module.

6

.4 Function chart

The following chart provides an overview of the switching
conditions depending on the adjusted mode and level.

Pump control, B mode

Dry adjustment

18

VEGAKON

66 - with transistor output

Set up

32650

-EN