7 maintenance and fault rectification, 1 maintenance, 2 remove interferences – VEGA VEGAWELL 51 4 … 20 mA_HART User Manual

Page 24: 7 m aintenance and fault recti fication

Advertising
background image

7 M

aintenance and fault recti

fication

7

.1 Maintenance

W

hen used in the correct way, no special maintenance is

required in normal operation.

7

.2 Remove interferences

T

he operator of the system is responsible for taken suitable

measures to remove interferences.

A

maximum of reliability is ensured. Nevertheless, faults can

occur during operation. These may be caused by the following,
e.g.:

l

S

ensor

l

P

rocess

l

V

oltage supply

l

S

ignal processing

T

he first measures to be taken are to check the output signals

as well as to evaluate the error messages via the indicating
and adjustment module. The procedure is described below.
F

urther comprehensive diagnostics can be carried out on a PC

with the software PACTware™ and the suitable DTM. In many
cases, the causes can be determined in this way and faults
can be rectified.

H

owever, should these measures not be successful, call the

VEGA

service hotline in urgent cases under the phone no. +49

1805 858550

.

T

he hotline is available to you 7 days a week round-the-clock.

S

ince we offer this service world-wide, the support is only

available in the English language. The service is free of
charge, only the standard telephone costs will be charged.

C

onnect a handheld multimeter in the suitable measuring

range according to the wiring plan.

?

4 … 20

mA signal not stable

l

L

evel fluctuations

à Adjust integration time via PACTware™

l

no atmospheric pressure compensation

à Check the capillaries and cut them clean

Reaction when malfunc-
tions occur

Causes of malfunction

Fault rectification

24

hour service hotline

Checking the 4 … 20 mA
signal

24

VEGAWELL

51 • 4 … 20

mA/HART

M

aintenance and fault rectification

32468

-EN

-080604

Advertising