be a place where no installations cross the microwave signals. Make
sure when planning your measurement loop that the radar signals
have a "clear view" to the product.

In case of existing vessel installations, a false echo storage should be
carried out during setup.

If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.

Fig. 14: Cover smooth profiles with deflectors

Air rinsing is useful for avoiding buildup, particularly when there is
strong condensation. Since VEGAPULS 67 has no direct rinsing air
connection, a separate rinsing air connection must be provided in the
mounting socket. By inclining this connection towards the top, a
particularly effective cleaning of the antenna cover is achieved.

Fig. 15: Purging air connection

Large material heaps are best measured with several instruments,
which can be mounted on e.g. traverse cranes. For this type of
application it is advantageous to orient the sensor perpendicular to the
bulk solid surface.

The sensors do not influence each other.

Information:
Keep in mind that for these applications, the sensors are designed for
relatively slow level changes. If the sensor is used on a movable boom,

Air rinsing

Material heaps

VEGAPULS

67 • Profibus PA

21