VEGA VEGAWAVE 63 - NAMUR User Manual

Page 24

Advertising
background image

Sensor cur-
rent

Level relay
amplifier -
overflow
protection

Level relay
amplifier -
dry run pro-
tection

Signal lamp
amplifier -
overflow
protection

Signal lamp
amplifier -
dry run pro-
tection

Signal lamp
- sensor

1. Low Current
(approx. 3 s)

approx. 1 mA energized

currentless

2. High Current
(approx. 1.5 s)

approx.
2.2 mA

currentless

energized

3. Return to the actual
operating condition

Note:
When used in measuring chains according to IEC 61508, mode B (dry
run protection) is not permitted.

You can carry out the function test with the stated current values also
directly with a safety PLC or a process control system.

Test passed

l

Low Current ≥ 2 s

l

High Current ≥ 1 s

Test not passed

l

Low Current < 2 s / > 4 s

l

High Current < 1 s / > 2 s

Test assessment (SPLC)

24

VEGAWAVE

63 • - NAMUR

6 Set up

32259

-EN

-120418

Advertising