VEGA VEGAWAVE 63 - NAMUR User Manual
Page 31
Fig. 31: Max. lateral load alongside fork side (narrow fork side)
Output variable
Output
Two-wire NAMUR output
Current consumption
-
Falling characteristics (max.)
≥
2.4 mA uncovered/≤ 1 mA covered
-
Rising characteristics (min.)
≤
1 mA uncovered/≥ 2.4 mA covered
-
Fault message
≤
1 mA
Necessary processing system
NAMUR processing system according to
IEC
60947-5-6 (EN 50227/DIN 19234)
Modes (NAMUR output adjustable to falling or rising characteristics)
-
Min.
rising characteristic curve (High current when
immersed)
-
Max.
falling characteristics (Low current when immersed)
Ambient conditions
Ambient temperature on the housing
-40 … +80 °C (-40 … +176 °F)
Storage and transport temperature
-40 … +80 °C (-40 … +176 °F)
Process conditions
Measured variable
Limit level of solids
Process pressure
-1 … 25 bar/-100 … 2500 kPa (-14.5 … 363 psig)
VEGAWAVE
63 of 316L
-50 … +150 °C (-58 … +302 °F)
Process temperature (thread or flange tem-
perature) with temperature adapter (option)
-50 … +250 °C (-58 … +482 °F)
VEGAWAVE
63 • - NAMUR
31
9 Supplement
32259
-
EN
-120418