3.2 Principle of operation

VEGAFLEX

67 is a level sensor with rod or cable probe for continuous

interface measurement.

It is designed for industrial use in all areas of process technology and
can be used in liquids.

High frequency microwave impulses are guided along a steel cable or
rod. When reaching the product surface, a part of the microwave
impulses is reflected. The other part passes the upper product and is
reflected a second time by the interface. The running times to the two
product layers are processed by the instrument.

Upper medium (L2)

l

The upper medium must not be conductive

l

The dielectric figure of the upper medium must be known (input
required). Min. dielectric figure: rod version 1.7. You can find a list
with the dielectric figures on our home page: www.vega.com

l

The composition of the upper medium must be stable, no varying
products or mixtures

l

The upper medium must be homogeneous, no stratifications within
the medium

l

Min. thickness of the upper medium 100 mm

l

Clear separation from the lower medium, no emulsion phase, no
mull layer

l

If possible, no foam on the surface

Lower medium (L1)

l

The dielectric figure must be 10 higher than the dielectric figure of
the upper medium, preferably electrically conductive. Example:
upper medium dielectric figure 2, lower medium at least dielectric
figure 12

Application range

Functional principle

Prerequisites for inter-
face measurement

8

VEGAFLEX

67 • Profibus PA