2 instructions for installation – VEGA VEGAFLEX 67 (-40…+150°C PFA insulated) 4 … 20 mA_HART four-wire User Manual

Page 12

Advertising
background image

Fig. 3: Measures against moisture penetration

T

he reference plane for the measuring range of the sensors is the

sealing surface of the thread or flange.

K

eep in mind that a min. distance must be maintained below the

reference plane and possibly also at the end of the probe -
measurement in these areas is not possible (dead band). Particularly
the cable length cannot be used all the way to the end because
measurement in the area of the gravity weight is not possible. These
min. distances (dead bands) are listed in chapter "Technical data".
K

eep in mind for the adjustment that the default setting for the

measuring range refers to water.

T

he process fitting must be sealed if there is gauge or low pressure in

the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.

T

he max. permissible pressure is specified in chapter "Technical data"

or on the type label of the sensor.

4

.2 Instructions for installation

W

hen mounting the cable and rod versions of VEGAFLEX 67 keep at

least a distance of 300 mm (11.81 in) to other vessel installations or to
the vessel wall.

D

uring operation, the probe must not touch any installations or the

vessel wall. If necessary, fasten the probe end.

I

n vessels with conical bottom it can be advantageous to mount the

sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the bottom. When using the cable version,

Measuring range

Pressure

Mounting position

12

VEGAFLEX

67 • 4 … 20

mA/HART - four-wire

4 M

ounting

32304

-EN

-120329

Advertising