Fig. 9: Alignment in liquids

The mounting location of the radar sensor should be a place where no
other equipment or fixtures cross the path of the microwave signals.

Vessel installations such as, for example, ladders, limit switches,
heating spirals, struts, etc. can cause false echoes that get super-
imposed on the useful echo. Make sure when planning your measuring
site that the radar sensor has a "clear view" to the measured product.

In case of existing vessel installations, a false echo storage should be
carried out during setup.

If large vessel installations such as struts or supports cause false
echoes, these can be attenuated through supplementary measures.
Small, inclined sheet metal baffles above the installations scatter the
radar signals and prevent direct interfering reflections.

Fig. 10: Cover smooth profiles with deflectors

If there are agitators in the vessel, a false echo storage should be
carried out with the agitators in motion. This ensures that the interfering
reflections from the agitators are saved with the blades in different
positions.

Vessel installations

Agitators

VEGAPULS

66 enamel • Profibus PA

17