3 operation – VEGA VEGACAL 69 4 … 20 mA_HART - two-wire User Manual

Page 9

Advertising
background image

9

3 Product description

VEGACAL 69 • 4 … 20 mA/HART - two-wire

31178-EN-130917

1

2

3

Fig. 3: Functional principle - Plate capacitor
1 Distance between the electrode surfaces

2 Size of the electrode surfaces

3 Type of dielectric between the electrodes

The two probes are the capacitor plates. The measured product is

the dielectric. Due to the higher dielectric constant of the product

compared to air, the capacitance increases as the material gradually

covers the probe.
The capacitance as well as the resistance change are converted by

the electronics module into a level-proportional signal.

4 … 20 mA/HART two-wire electronics for voltage supply and meas-

ured value transmission on the same cable.
The supply voltage range can differ depending on the instrument

version.
The data for power supply are specified in chapter "Technical data".
The optional background lighting of the display and adjustment

module is powered by the sensor. A certain level of operating voltage

is required for this. You can find the exact voltage specifications in

chapter "Technical data".
The optional heating requires its own operating voltage. You can find

details in the supplementary instructions manual "Heating for display

and adjustment module".
This function is generally not available for approved instruments.

3.3 Operation

The instrument can be adjusted with the following adjustment media:

With the display and adjustment module

with the suitable VEGA DTM in conjunction with an adjustment

software according to the FDT/DTM standard, e.g. PACTware and

PC

with manufacturer-specific adjustment programs AMS™ or PDM

With a HART handheld

Voltage supply

Advertising