5 set up, 1 general information, 2 adjustment elements – VEGA VEGAWAVE S 61 User Manual

Page 17: 3 functional chart, 5 s et up

Advertising
background image

5 S

et up

5

.1

General information

Function/Configuration
On the electronics module you will find the
following indicating and adjustment elements:

l

DIL switch for density adaptation

l

DIL switch for mode adjustment - min./max.

l

Signal lamp (LED)

5

.2

Adjustment elements

Density adaptation
With this DIL switch, the switching point can be set
to bulk solids having a density between 0.1 and
0.3

g/cm³.

As default setting, the switch of VEGAWAVE S 61
is set to the large weight symbol (> 0.03 g/cm³). In

very light solids you should turn the DIL switch to
the small weight symbol (0.1 … 0.3 g/cm³). By
doing this, VEGAWAVE S 61 is more sensitive and
can detect light solids reliably.

Mode adjustment
With the mode adjustment (min./max.) you can
change the switching condition of the relay. You
can set the required mode according to the
"Function chart" (max. - max. detection or overfill

protection, min. - min. detection or dry run
protection).

We recommend connecting according to the
quiescent current principle (relay contact deener-
gizes when the switching point is reached),
because the relay always takes on the same (safe)
condition if a failure is detected.

Control lamp
Control lamp (LED) for indication of the switching
condition

l

green = relay energized

l

red = relay deenergized

l

red (flashing) = failure

5

.3

Functional chart

The following chart provides an overview of the
switching conditions depending on the adjusted
mode and level.

Level

Switching
status

Control
lamp

Mode max.
Overflow pro-
tection

Relay ener-

gized

or

transistor con-

ducts

Green

Mode max.
Overflow pro-
tection

Relay deener-

gized

or

transistor

blocks

Red

Mode min.
Dry run pro-
tection

Relay ener-

gized

or

transistor con-

ducts

Green

Mode min.
Dry run pro-
tection

Relay deener-

gized

or

transistor

blocks

Red

Failure of the
supply voltage
(

min./max.

mode)

any

Relay deener-

gized

or

transistor

blocks

Failure

any

Relay deener-

gized

or

transistor

blocks

ashes red

VEGAWAVE S 61

17

Set up