4 Mounting

4.1 General instructions

The module cards of VEGALOG 571 can only be mounted into

the 19" carrier BGT LOG 571. It is provided with a special bus

board for data transmission between CPU and the individual

peripheral cards (LOGBUS). The carrier is designed for

mounting into a switching cabinet or 19" housing.
The plug position for the individual cards is individually

selectable, the system saves the card positions when switch-

ing on.

Note:

The plug positions must not be changed after the parameter

adjustment because measurement loops that have already

been set up would otherwise have to be reconfigured.

4.2 Module

Provide a module for the VEGALOG 571 EA card. You will find

the description in the operating instructions manual "CPU and

carrier".
In Ex applications, an additional separator must be used. The

following types can be used:

l

VEGATRENN 149A (additional supply voltage, particularly

suitable for long cable lengths)

l

KFD0-CS-Ex1.51P (no additional supply voltage neces-

sary)

Mounting of both types is carried out on a standard carrier rail.

Further details are available in the respective operating

instructions manual.

4.3 Coding

A mechanical coding system avoids later interchanging of the

various module cards in the carrier.
The coding system consists of:

l

two coded pins in the multipoint connector

l

two holes in the male multipoint connector of the respective

component

The coded pins are attached to the module.