4 mounting steps external housing – VEGA VEGABAR 63 Profibus PA User Manual
Page 14
à Screw VEGABAR 63 into the welded socket. Tighten the hexagon
on the process fitting with a suitable wrench. Wrench size, see
chapter "Dimensions".
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
4.4 Mounting steps external housing
1
Mark the holes according to the following drilling template
2
Depending on the mounting surface, fasten the wall mounting
plate with 4 screws
90 mm (3.54")
R 3,5 mm
(0.14")
3mm
(0.12")
70 mm (2.76")
8 mm
(0.32")
93 mm (3.66")
110 mm (4.33")
Fig. 5: Drilling template - wall mounting plate
Tip:
Mount the wall mounting plate so that the cable entry of the socket
housing points downward. The socket housing can be displaced by
180° to the wall mounting plate.
Warning:
The four screws of the socket housing must only be hand-screwed. A
torque > 5 Nm (3.688 lbf ft) can damage the wall mounting plate.
Wall mounting
14
VEGABAR
63 • Profibus PA
4 Mounting
32463
-EN
-081209