VEGA VEGAFLEX 62 4 … 20 mA_HART two-wire User Manual
Page 17
Advertising
I
f possible, avoid sockets. Mount the sensor flush with the vessel top. If
this is not possible, use short sockets with small diameter.
H
igher sockets or sockets with a bigger diameter can generally be
used. They simply increase the upper dead band. Check if this is
relevant for your measurement.
I
n such cases, always carry out a gating out of false signals after
installation. You can find further information under "Setup procedure".
h
d
d
h
DN40 ... DN150
£ 150
> DN150 ... DN200
£ 100
Fig. 8: Mounting socket
W
hen welding the socket, make sure that the socket is flush to the
vessel wall.
1
2
Fig. 9: Socket must be installed flush
1
Unfavourable installation
2
Socket flush - optimum installation
Socket
VEGAFLEX
62 • 4 … 20
mA/HART two-wire
17
4 M
ounting
31837
-
EN
-100426
Advertising