VEGA VEGAFLEX 62 4 … 20 mA_HART two-wire User Manual

Page 17

Advertising
background image

I

f possible, avoid sockets. Mount the sensor flush with the vessel top. If

this is not possible, use short sockets with small diameter.

H

igher sockets or sockets with a bigger diameter can generally be

used. They simply increase the upper dead band. Check if this is
relevant for your measurement.

I

n such cases, always carry out a gating out of false signals after

installation. You can find further information under "Setup procedure".

h

d

d

h

DN40 ... DN150

£ 150

> DN150 ... DN200

£ 100

Fig. 8: Mounting socket

W

hen welding the socket, make sure that the socket is flush to the

vessel wall.

1

2

Fig. 9: Socket must be installed flush

1

Unfavourable installation

2

Socket flush - optimum installation

Socket

VEGAFLEX

62 • 4 … 20

mA/HART two-wire

17

4 M

ounting

31837

-

EN

-100426

Advertising