Quick start – VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART two-wire User Manual

Page 2

Advertising
background image

2

Quick start

VEGAPULS 63 • 4 … 20 mA/HART two-wire

36511-EN-130228

Quick start

The quick start procedure enables a quick setup with many applica-

tions. You can find further information in the respective chapters of the

operating instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should

protrude > 10 mm into the vessel

ca

. 10 mm

> 200 mm

(7.87")

Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling

2. Note min. socket diameter depending on the socket length
For further information see chapter "Mounting".
1. Make sure that the power supply corresponds to the specifica-

tions on the type label.

2. Connect the instrument according to the following illustration

5

1

2

+

( )

(-)

6 7 8

4...20mA

2

3

4

1

Fig. 2: Electronics and connection compartment, single chamber housing
1 Voltage supply, signal output

2 For display and adjustment module or interface adapter

3 For external display and adjustment unit

4 Ground terminal for connection of the cable screen

For further information see chapter "Connecting to power supply".
1. Go via the display and adjustment module to the menu "Setup".

2. In the menu item "Medium"you select the medium of your applica-

tion, for example "Aqueous solution".

3. Select in the menu item "Application" the vessel, the application

and the vessel form, for example, storage tank.

Mounting

Electrical connection

Set parameters

Advertising