11 Supplement

VEGAPULS 63 • 4 … 20 mA/HART two-wire

36511-EN-130228

3

4

2

1

Fig. 47: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Length antenna cone

4 Useful measuring range

Standard electronics
Max. measuring range

35 m (114.8 ft)

Recommended measuring range

Ʋ Flange DN 50, 2"

up to 15 m (49.21 ft)

Ʋ Flange DN 80, 3"

up to 35 m (114.8 ft)

Electronics with increased sensitivity
Max. measuring range

75 m (246.1 ft)

Flange DN 50, 2"

up to 15 m (49.21 ft)

Flange DN 80, 3"

up to 35 m (114.8 ft)

Output variable
Output signal

4 … 20 mA/HART

Fulfilled HART specification

7.0

Signal resolution

0.3 µA

Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA
Max. output current

22 mA

Starting current

≤ 3.6 mA; ≤ 10 mA for 5 ms after switching on

Load

see load diagram under Power supply

Damping (63 % of the input variable),

adjustable

0 … 999 s

HART output values according to HART 7.0

1)

Ʋ PV (Primary Value)

Distance to the level

Ʋ SV (Secondary Value)

Level as percentage value

Ʋ TV (Third Value)

Linearised percentage value

1)

Default values, can be assigned individually