6 Set up with the indicating and adjustment module

VEGAPULS 61 • Profibus PA

36501-EN-121011

by the user, particularly when setting the switching point on the level

switch.

When a reset is carried out, all settings (with only a few exceptions)

are reset. The exceptions are: PIN, language, lighting, SIL and HART

mode.

The following reset functions are available:

Delivery status: Restoring the parameter settings at the time of

shipment from the factory incl. the order-specific settings. A cre-

ated false signal suppression, user-programmable linearization

curve, measured value memory as well as event memory will be

deleted.

Basic settings: Resetting of the parameter settings incl. special

and laboratory parameters to the default values of the respective

instrument. Any created false signal suppression, user program-

mable linearization curve, measured value memory as well as

event memory will be deleted.

Setup: Resetting of the parameter settings to the default values of

the respective instrument . Order-related settings remain but are

not taken over into the current parameters. User-generated false

signal suppression, user-programmed linearization curve, meas-

ured value memory, echo curve memory as well as event memory

remain untouched. The linearization is set to linear.

False signal suppression: Deleting a previously created false

signal suppression. The false signal suppression created in the

factory remains active.

Peak values measured value: Resetting of the measured min.

and max. distances to the actual measured value.

Select the requested reset function [->] and confirm with [OK].
The following table shows the default values of VEGAPULS 61: