VEGA VEGABAR 55 Foundation Fieldbus User Manual

Page 46

Advertising
background image

46

10 Supplement

VEGABAR 55 • Foundation Fieldbus

36736-EN-130321

Ʋ Connection cable with IP 68 1 bar

version

PE, PUR

Weight approx.

0.8 … 8 kg (1.764 … 17.64 lbs), depending on process

fitting

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Channel Numbers

Ʋ Channel 1

Primary value

Ʋ Channel 2

Secondary value 1

Ʋ Channel 3

Secondary value 2

Ʋ Channel 4

Temperature value

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Dynamic behaviour output
Run-up time approx.

10 s

90 %

100 %

10 %

t

t

T

A

t

t

S

2

1

Fig. 26: Sudden change of the process variable. t

T

: dead time; t

A

: rise time; t

S

: jump response time

1 Process variable

2 Output signal

Dead time

≤ 150 ms

Rise time

≤ 100 ms (10 … 90 %)

Step response time

≤ 250 ms (ti: 0 s, 10 … 90 %)

Damping (63 % of the input variable)

0 … 999 s, adjustable

Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:

Ʋ Percentage value

-10 … 110 %

Ʋ Pressure value

-20 … 120 %

Advertising