3 Product description

VEGABAR 55 • Foundation Fieldbus

36736-EN-130321

This operating instructions manual applies to the following instrument

versions:

Software from 3.82

3.2 Principle of operation

VEGABAR 55 is a pressure transmitter for use in the chemical, food

processing and pharmaceutical industries. Depending on the version,

it is used for level, gauge, absolute pressure or vacuum measure-

ment. Measured products are gases, vapours and liquids, also those

with higher temperatures.

The METEC

®

measuring cell is the measuring unit. It consists of

the ceramic-capacitive CERTEC

®

measuring cell and a special,

temperature-compensated isolating system.
The hydrostatic pressure of the product or the process pressure

causes a capacitance change in the measuring cell via the metallic

process diaphragm and the isolating liquid. This change is converted

into a corresponding output signal.

Power is supplied via the H1 Fieldbus. A two-wire cable according to

Fieldbus specification serves as carrier of both power and digital data

for multiple sensors. This cable can be operated in two versions:

via an H1 interface card in the control system and additional power

supply

via a Linking device with HSE (High speed Ethernet) and addi-

tional power supply according to IEC 61158-2

The DD (Device Descriptions) and CFF (capability files) necessary

for planning and configuration of your FF (Foundation Fieldbus) com-

munication network are available in the download area of the VEGA

homepage www.vega.com under "Services - Downloads - Software

- Foundation Fieldbus". The appropriate certificates are also available

there. A CD with the appropriate files and certificates can be ordered

via e-mail under [email protected] or by phone from one of the

VEGA agencies under the order number "DRIVER.S".
The backlight of the display and adjustment module is powered by the

sensor. Prerequisite is a certain level of operating voltage.
The data for power supply are specified in chapter "Technical data".
The optional heating requires its own operating voltage. You can find

details in the supplementary instructions manual "Heating for display

and adjustment module".
This function is generally not available for approved instruments.

3.3 Operation

The instrument can be adjusted with the following adjustment media:

With the display and adjustment module

with the suitable VEGA DTM in conjunction with an adjustment

software according to the FDT/DTM standard, e.g. PACTware and

PC

Scope of this operating

instructions manual

Application area

Functional principle

Power supply and bus

communication

DD/CFF