10 Supplement

VEGABAR 55 • Foundation Fieldbus

36736-EN-130321

Deviation determined according to the limit point method according to IEC 60770

10)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation with version 0.075 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.075 %

Ʋ Turn down > 5 : 1

< 0.015 % x TD

Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Deviation with absolute pressure measuring range 0.1 bar

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.25 %

Ʋ Turn down > 5 : 1

< 0.05 % x TD

Influence of the product or ambient temperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Thermal change zero signal and output span, reference temperature 20 °C (68 °F):

Ʋ In the compensated temperature

range 0 … +100 °C (+32 … +212 °F)

< (0.05 % + 0.1 % x TD)

Ʋ Outside the compensated tempera-

ture range

< (0.05 % + 0.15 % x TD)

Thermal change, current output
Applies also to the analogue 4 … 20 mA current output and refers to the set span.
Thermal change, current output

< 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C

(-40 … +176 °F)

0,15 %

-0,15 %

-40°C

-20°C

20°C

40°C

60°C

80°C

Fig. 27: Thermal change, current output

10)

Incl. non-linearity, hysteresis and non-repeatability.