Ac b d – VEGA Float for oil_water detection for VEGASWING 63 and EL 3 User Manual

Page 11

Advertising
background image

A

C

B

D

2

1

3

Fig. 4: Switching status of the measuring system
A

No liquid present

B

Water > 25 mm (> 1 in)

C

Oil > 25 mm (> 1 in)

D

Oil layer on water, layer thickness > 50 mm (> 2 in)

1

Liquid height water > 25 mm (> 1 in)

2

Liquid level oil > 25 mm (> 1 in)

3

Layer thickness oil > 50 mm (> 2 in)

Note:
Keep in mind that the conductive electrode responds a little earlier
when being covered with water to ensure a reliable detection of water
(to avoid false alarm).

The level switch VEGASWING 63 must be oeprated in mode A (overfill
protection).

The sensitivity switch of VEGASWING 63 must be set to density 0.7 g/
cm

3

.

The conductive electrode EL 3 must be operated in max. mode
(overflow protection).

Immerse the two electrode rods approximately 10 mm (0.4 in) into
water.

Carry out an adjustment on the corresponding signal conditioning
instrument. The adjustment is described in the operating instructions
of the signal conditioning instrument.

Settings - VEGASWING
63

Settings - EL 3

Float for oil/water detection • for VEGASWING 63 and EL 3

11

6 Setup

36676

-

EN

-120124

Advertising