6 Set up with the display and adjustment module

VEGAPULS 63 • HART and accumulator pack

40794-EN-130228

When non-contact level sensors are used, the measurement can be

influenced by the respective process conditions. In this menu item,

the measurement reliability of the level echo is displayed as dB value.

The measurement reliability equals signal strength minus noise. The

higher the value, the more reliable the measurement. With a function-

ing measurement, the values are > 10 dB.

The "Echo curve" shows the signal strength of the echoes over the

measuring range in dB. The signal strength enables an evaluation of

the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see

menu "Additional settings") of the empty vessel with signal strength in

"dB" over the measuring range.

A comparison of echo curve and false signal suppression allows a

more accurate conclusion on measurement reliability. The selected

curve is continuously updated. With the [OK] key, a submenu with

zoom functions is opened:

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

With the function "Echo curve memory" the echo curve can be saved

at the time of setup. This is generally recommended; for using the As-

set Management functions it is absolutely necessary. If possible, the

curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolu-

tion echo curve can be displayed and used to recognize signal

Diagnosis - Measurement

reliability

Diagnoses - Curve indica-

tion

Diagnostics - Echo curve

memory