VEGA VEGAPULS 63 (≥ 2.0.0 - ≥ 4.0.0) HART and accumulator pack User Manual

Page 57

Advertising
background image

57

11 Supplement

VEGAPULS 63 • HART and accumulator pack

40794-EN-130228

0,5 m (1.6 ft)

10 mm (0.394 in)

- 10 mm (- 0.394 in)

0

2 mm (0.079 in)

- 2 mm (- 0.079 in)

1 2

3

Fig. 41: Deviation under reference conditions
1 Reference plane

2 Antenna edge

3 Recommended measuring range

Repeatability

≤ ±1 mm

Variables influencing measurement accuracy
Specifications apply to the HART signal and the current output
Temperature drift - Digital output

±3 mm/10 K relating to the max. measuring range or

max. 10 mm

Additional deviation through electromag-

netic interference acc. to EN 61326

< ±50 mm

Specifications apply also to the current output
Temperature drift - Current output

±0.03 %/10 K relating to the 16 mA span max. ±0.3 %

Deviation on the current output by ana-

logue/digital conversion

< ±15 µA

Deviation on the current output due to

strong, high frequency electromagnetic

fields acc. to EN 61326

< ±150 µA

Influence of the superimposed gas and pressure to the accuracy
The propagation speed of the radar impulses in gas or vapour above the medium is reduced by

high pressure. This effect depends on the superimposed gas or vapour and is especially large at

low temperatures.
The following table shows the resulting deviation for some typical gases and vapours. The specified

values refer to the distance. Positive values mean that the measured distance is too large, negative

values that the measured distance is too small.

Gas phase

Temperature

Pressure

1 bar

(14.5 psig)

10 bar

(145 psig)

50 bar

(725 psig)

100 bar

(1450 psig)

200 bar

(2900 psig)

Air

20 °C/68 °F

0.00 %

0.22 %

1.2 %

2.4 %

4.9 %

200 °C/392 °F -0.01 %

0.13 %

0.74 %

1.5 %

3.0 %

400 °C/752 °F -0.02 %

0.08 %

0.52 %

1.1 %

2.1 %

Advertising