VEGA VEGAPULS WL 61 Foundation Fieldbus User Manual

Page 20

Advertising
background image

20

4 Mounting

VEGAPULS WL 61 • Foundation Fieldbus

38063-EN-121011

d

h

h

300 mm / 11.8"

d

80 mm / 3.15"

100 mm / 4"

125 mm / 5"
150 mm / 6"

500 mm / 19.69"

600 mm / 23.6"
800 mm / 31.5"

Fig. 18: Deviating socket dimensions

Direct the sensor as perpendicular as possible to the product surface

to achieve optimum measurement results.

Fig. 19: Orientation of the sensor

The mounting location of the radar sensor should be a place where no

other equipment or fixtures cross the path of the microwave signals.
Vessel installations, such as e.g. ladders, limit switches, heating spi-

rals, struts, etc., can cause false echoes and impair the useful echo.

Make sure when planning your measuring site that the radar sensor

has a "clear view" to the measured product.
In case of existing vessel installations, a false echo storage should be

carried out during setup.
If large vessel installations such as struts or supports cause false

echoes, these can be attenuated through supplementary measures.

Small, inclined sheet metal baffles above the installations scatter the

radar signals and prevent direct interfering reflections.

Fig. 20: Cover smooth profiles with deflectors

Sensor orientation

Vessel installations

Advertising