4 measurement error during emptying – VEGA VEGAPULS WL 61 Foundation Fieldbus User Manual

Page 34

Advertising
background image

34

7 Diagnosis, Asset Management and service

VEGAPULS WL 61 • Foundation Fieldbus

38063-EN-121011

Fault description

Error pattern

Cause

Rectification

9. Measured value

jumps sporadically to

100 % during filling

Level

time

0

– Varying condensation or con-

tamination on the antenna

– Carry out a false signal sup-

pression or increase false

signal suppression with con-

densation/contamination in the

close range by editing

10. Measured value

jumps to ≥ 100 % or

0 m distance

Leve

l

time

0

– Level echo is no longer

detected in the close range

due to foam generation or false

echoes in the close range. The

sensor goes into overfill protec-

tion mode. The max. level (0 m

distance) as well as the status

message "Overfill protection"

are outputted.

– Check measuring site: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Use a sensor with a more suit-

able antenna

7.4 Measurement error during emptying

Fault description

Error pattern

Cause

Rectification

11. Measured value re-

mains unchanged in

the close range during

emptying

Level

time

0

– False signal larger than the

level echo

– Level echo too small

– Remove false echoes in the

close range. Check: Antenna

must protrude out of the socket

– Remove contamination on the

antenna

– Minimize interfering instal-

lations in the close range by

changing the polarization

direction

– After removing the false ech-

oes, the false signal suppres-

sion must be deleted. Carry out

a new false signal suppression

12. Measured value

jumps towards 0 %

during emptying

Level

time

0

– Echo from the tank bottom

larger than the product echo,

for example, with products with

ε

r

< 2.5 oil-based, solvents

– Check application parameters

Medium type, Vessel height and

Floor form, adapt if necessary

13. Measured value

jumps sporadically to-

wards 100 % during

emptying

Level

time

0

– Varying condensation or con-

tamination on the antenna

– Carry out false signal suppres-

sion or increase false signal

suppression in the close range

by editing

– With bulk solids, use radar sen-

sor with purging air connection

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Setup" must be carried out again or must

be checked for plausibility and completeness.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside the normal working hours on

seven days a week around the clock.
Since we offer this service worldwide, the support is in the English

language. The service itself is free of charge, the only costs involved

are the normal call charges.

Reaction after fault recti-

fication

24 hour service hotline