9.3 Supplementary information Foundation Fieldbus

The following table gives you an overview of the instrument versions and the corresponding device

descriptions, the electrical characteristics of the bus system as well as the applied function blocks.

Revisions Data

DD-Revision

Rev_01

CFF-File

010101.cff

Device Revision

0101.ffo
0101.sym

Cff-Revision

xx xx 01

Device software revision

> 4.4.0

ITK (Interoperability Test Kit) Number

5.0.2

Electricial Characteristics

Physicial Layer Type

Low-power signaling, bus-pow-

ered, FISCO I.S.

Input Impedance

> 3000 Ohms between

7.8 KHz - 39 KHz

Unbalanced Capacitance

< 250 pF to ground from either

input terminal

Output Amplitude

0.8 V P-P

Electrical Connection

2 Wire

Polarity Insensitive

Yes

Max. Current Load

10 mA

Device minimum operating voltage

9 V

Transmitter Function Blocks

Resource Block (RB)

1

Transducer Block (TB)

1

Standard Block (AI)

3

Execution Time

30 mS

Advanced Function Blocks

Discret Input (DI)

Yes

PID Control

Yes

Output Splitter (OS)

Yes

Signal Characterizer (SC)

Yes

Integrator

Yes

Input Selector (IS)

Yes

Arithmetic (AR)

Yes