Quick start – VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) HART - integrated accumulator User Manual

Page 2

Advertising
background image

2

Quick start

VEGAPULS 61 • HART - integrated accumulator

40792-EN-121011

Quick start

The quick start enables a quick setup with many applications. You

can find further information in the respective chapters of the operating

instructions manual.
1. Distance from the vessel wall > 200 mm, the antenna should

protrude > 10 mm into the vessel

ca

. 10 mm

> 200 mm

(7.87")

Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling

2. Note min. socket diameter depending on the socket length
For further information see chapter "Mounting".
1. Insert the battery charger into the socket of the power supply

compartment and load the integrated accumulator before setting

up the instrument.

2. Switch on the instrument by means of the button outside on the

housing.

1

Fig. 2: Switch on/off button outside on the housing
1 On/Off button

For further information see chapter "Connecting to power supply".
1. Go via the indicating and adjustment module to the menu "Setup".

2. In the menu item "Medium"you select the medium of your applica-

tion, for example "Aqueous solution".

3. Select in the menu item "Application" the vessel, the application

and the vessel form, for example, storage tank.

Mounting

Connect electrically

Set parameters