4 Mounting

VEGAPULS 68 • Foundation Fieldbus

36538-EN-121011

ficient air flow (the air is led through the holes to the feed system. A

rinsing of the whole parabolic antenna is not intended).

1

2
3

4

Fig. 6: Dismounting, parabolic antenna
1 Connection piece

2 Compression nut

3 Locknut

4 Parabolic antenna

4.4 Instructions for installation

The illustrations with the following mounting instructions show a radar

sensor with horn antenna. The mounting instructions apply analo-

gously also to the version with parabolic antenna.

The emitted radar impulses of the radar sensor are electromagnetic

waves. The polarisation plane is the direction of the electrical wave

component. By turning the instrument in the connection flange or

mounting boss, the polarisation can be used to reduce the effects of

false echoes.
The position of the polarisation plane is marked on the process fitting

of the instrument.

1

2

Fig. 7: Position of the polarisation level
1 Marking with screwed version

2 Marking with flange version

Mount the sensor at least 200 mm (7.874 in) away from the vessel

wall.

Horn and parabolic

antenna

Polarisation plane

Installation position