VEGA VEGAPULS 68 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 64

Advertising
background image

64

11 Supplement

VEGAPULS 68 • Foundation Fieldbus

36538-EN-121011

Input variable
Measured variable

The measured quantity is the distance between process

fitting of the sensor and product surface. The reference

plane is the seal surface on the hexagon or the lower

side of the flange.

3

4

2

1

Fig. 52: Data of the input variable
1 Reference plane

2 Measured variable, max. measuring range

3 Antenna length

4 Useful measuring range

Max. measuring range

75 m (246.1 ft)

Recommended meas. range depending on the antenna diameter

Ʋ ø 40 mm (1.575 in)

up to 15 m (49.21 ft)

Ʋ ø 48 mm (1.89 in)

up to 20 m (65.62 ft)

Ʋ ø 75 mm (2.953 in)

up to 40 m (131.2 ft)

Ʋ ø 95 mm (3.74 in)

up to 50 m (164 ft)

Ʋ Parabolic antenna

up to 75 m (246.1 ft)

Output variable
Output

Ʋ Signal

digital output signal, Foundation Fieldbus protocol

Ʋ Physical layer

according to IEC 61158-2

Damping (63 % of the input variable)

0 … 999 s, adjustable

Channel Numbers

Ʋ Channel 1

Process value

Ʋ Channel 8

Electronics temperature

Ʋ Channel 9

Count rate

Transmission rate

31.25 Kbit/s

Current value

Ʋ Non-Ex and Ex ia instrument

10 mA, ±0.5 mA

Ʋ Ex d instruments

16 mA, ±0.5 mA