4 Mounting
VEGAPULS 68 • Foundation Fieldbus
36538-EN-121011
Fig. 19: Agitators
Large material heaps are detected with several sensors, which can be
mounted on e.g. traverse cranes. For this type of application, it is best
to orient the sensor toward the solid surface. A mutual infuence of the
sensors is not possible.
Fig. 20: Radar sensors on traverse crane
Information:
Keep in mind that for these applications, the sensors are designed for
relatively slow level changes. When using VEGAPULS 68 on a mov-
able bracket, the max. measuring rate must be observed (see chapter
"Technical data").
Instruments for a temperature range up to 250 °C or up to 450 °C
have a distance piece between process fitting and electronics hous-
ing. Ths distance piece is used for thermal decoupling of the electron-
ics against high process temperatures.
Information:
The distance piece must only be incorporaed up to max. 50 mm in
the vessel installation. Only then, a reliable temperature decoupling is
guaranteed.
Material heaps
Mounting in the vessel
insulation