4 Mounting

VEGAPULS SR 68 • Foundation Fieldbus

38297-EN-130624

Fig. 19: Agitators

Large material heaps are detected with several sensors, which can be

mounted on e.g. traverse cranes. For this type of application, it is best

to orient the sensor toward the solid surface. A mutual infuence of the

sensors is not possible.

Fig. 20: Radar sensors on traverse crane

Information:

Keep in mind that for these applications, the sensors are designed

for relatively slow level changes. When using VEGAPULS SR 68 on

a movable bracket, the max. measuring rate must be observed (see

chapter "Technical data").

Instruments for a temperature range up to 250 °C or up to 450 °C

have a distance piece between process fitting and electronics hous-

ing. Ths distance piece is used for thermal decoupling of the electron-

ics against high process temperatures.
Information:

The distance piece must only be incorporated up to max. 50 mm in

the vessel isolation. Only then, a reliable temperature decoupling is

guaranteed.

Material heaps

Mounting in the vessel

insulation