4 rectify faults – VEGA VEGAPULS SR 68 Foundation Fieldbus User Manual

Page 61

Advertising
background image

61

9 Diagnosis, Asset Management and service

VEGAPULS SR 68 • Foundation Fieldbus

38297-EN-130624

9.4 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

The first measures are:

Evaluation of fault messages, for example via the display and

adjustment module

Checking the output signal

Treatment of measurement errors

Further comprehensive diagnostics options offer a PC with the soft-

ware PACTware and the suitable DTM. In many cases, the reasons

can be determined in this way and faults can be rectified.

The below tables show typical examples for application-relevant

measurement errors with bulk solids. There are two measurement

errors:

Constant level

Filling

Emptying

The images in column "Error pattern" show the real level with a bro-

ken line and the level displayed by the sensor as a continuous line.

1
2

Level

time

0

1 Real level

2 Level displayed by the sensor

Notes:

Wherever the sensor displays a constant value, the reason could

also be the fault setting of the current output to "Hold value"

In case of a too low level indication, the reason could be a line

resistance that is too high

Reaction when malfunc-

tions occur

Procedure for fault recti-

fication

Treatment of measure-

ment errors with bulk

solids

Advertising