4 setup steps – VEGA VEGABAR 54 Foundation Fieldbus - climate compensated User Manual

Page 26

Advertising
background image

26

6 Set up with the display and adjustment module PLICSCOM

VEGABAR 54 • Foundation Fieldbus - climate compensated

36791-EN-130321

– Save value

[->] key to select:

– Menu change

– Select list entry

– Select editing position

[+] key:

– Change value of the parameter

[ESC] key:

– interrupt input

– Jump to next higher menu

The sensor is adjusted via the four keys of the display and adjust-

ment module. The LC display indicates the individual menu items. The

functions of the individual keys are shown in the above illustration.

Approx. 10 minutes after the last pressing of a key, an automatic reset

to measured value indication is triggered. Any values not confirmed

with [OK] will not be saved.

6.4 Setup steps

In HART-Multidrop mode (several sensors on one input) the address

must be set before continuing with the parameter adjustment. You

will find a detailed description in the operating instructions manual

"Display and adjustment module" or in the online help of PACTware

or DTM.

HART mode

Standard

Address 0

VEGABAR 54 can be used for level as well as for process pressure

measurement. Default setting is level measurement. The mode can be

changed in the adjustment menu.
Depending on the application only the respective subchapter "Level

or process pressure measurement" is of importance. There, you find

the individual adjustment steps.
Level measurement
Set up VEGABAR 54 in the following sequence:
1. Selecting adjustment unit/density unit
2. Carry out a position correction
3. Carry out min. adjustment
4. Carry out max. adjustment
In the menu item "Adjustment unit" you select the physical unit in

which the adjustment should be carried out, e.g. mbar, bar, psi…
The position correction compensates the influence of the mounting

position or static pressure on the measurement. It does not influence

the adjustment values.

Adjustment system

Address setting HART

multidrop

Level or process pres-

sure measurement

Parameter adjustment

"Level measurement"

Advertising