Deviation determined according to the limit point method according to IEC 60770

11)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation with version 0.1 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.1 %

Ʋ Turn down > 5 : 1

< 0.02 % x TD

Deviation with version 0.2 %

Ʋ Turn down 1 : 1 up to 5 : 1

< 0.2 %

Ʋ Turn down > 5 : 1

< 0.04 % x TD

Influence of the product or ambient temperature
Average temperature coefficient of the zero signal
Applies to digital interfaces (HART, Profibus PA, Foundation Fieldbus) as well as to analogue

current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal measuring

range/set span.

Nominal measuring range in

bar/kPa

Nominal

measuring

range in psig

Average temperature coef-

ficient of the zero signal, in

the compensated temper-

ature range 0 … +100 °C

(+32 … +212 °F), reference

temperature 20 °C (68 °F)

Average temperature co-

efficient of the zero signal,

outside the compensated

temperature range

0 … 0.2 bar/0 … 20 kPa

0 … 3 psig

< (0.05 + 0.05 x TD)%/10K

< (0.05 + 0.1 x TD)%/10K

0 … 0.4 bar/0 … 40 kPa

0 … 6 psig

< (0.05 + 0.05 x TD)%/10K

< (0.05 + 0.1 x TD)%/10K

0 … 1 bar/0 … 100 kPa

0 … 15 psig

< (0.02 + 0.05 x TD)%/10K

< (0.02 + 0.1 x TD)%/10K

0 … 2.5 bar/0 … 250 kPa

0 … 35 psig

< (0.02 + 0.05 x TD)%/10K

< (0.02 + 0.1 x TD)%/10K

0 … 5 bar/0 … 500 kPa

0 … 70 psig

< (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

0 … 10 bar/0 … 1000 kPa

0 … 150 psig < (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

0 … 25 bar/0 … 2500 kPa

0 … 350 psig < (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

0 … 60 bar/0 … 6000 kPa

0 … 900 psig < (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-1 … 0 bar/-100 … 0 kPa

-15 … 0 psig

< (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-1 … 1.5 bar/-100 … 150 kPa -15 … 25 psig < (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-1 … 5 bar/-100 … 500 kPa

-15 … 70 psig < (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-1 … 10 bar/-100 … 1000 kPa -

15 … 150 psig

< (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-1 … 25 bar/-100 … 2500 kPa -

15 … 350 psig

< (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-1 … 60 bar/-100 … 6000 kPa -

15 … 900 psig

< (0.02 + 0.03 x TD)%/10K

< (0.04 + 0.06 x TD)%/10K

-0.1 … 0.1 bar/-10 … 10 kPa

-

1.5 … 1.5 psig

< (0.05 + 0.05 x TD)%/10K

< (0.05 + 0.1 x TD)%/10K

-0.2 … 0.2 bar/-20 … 20 kPa

-3 … 3 psig

< (0.05 + 0.05 x TD)%/10K

< (0.05 + 0.1 x TD)%/10K

-0.5 … 0.5 bar/-50 … 50 kPa

-7 … 7 psig

< (0.05 + 0.05 x TD)%/10K

< (0.02 + 0.1 x TD)%/10K

11)

Incl. non-linearity, hysteresis and non-repeatability.