3 wiring plan, single chamber housing – VEGA VEGAMIP R61 Receiving unit - Relay User Manual

Page 25

Advertising
background image

5

.3 Wiring plan, single chamber housing

We recommend connecting VEGAMIP 61 in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe condition).

Information:
The relays are always shown in non-operative condition.

3

2

1

Fig. 16: Wiring plan receiving unit - VEGAMIP 61 (receiver)

1

Relay output

2

Relay output

3

Voltage supply

When connecting to a PLC, the min. switching capacity of the relay
must be taken into account.

If ncecssary, a correspondingly dimensioned resistor must be
connected in parallel to the PLC input. With a voltage U

B

von 24 V and

a PLC inner resistance R

i

>

100 kΩ, the additional load resistance R

L

must be between 6.8 and 8.2 kΩ.

Wiring plan

Connection to a PLC

VEGAMIP R

61 • - Relay

25