3 wiring plan, single chamber housing – VEGA VEGAMIP R61 Receiving unit - Relay User Manual
Page 25
5
.3 Wiring plan, single chamber housing
We recommend connecting VEGAMIP 61 in such a way that the
switching circuit is open when there is a level signal, line break or
failure (safe condition).
Information:
The relays are always shown in non-operative condition.
3
2
1
Fig. 16: Wiring plan receiving unit - VEGAMIP 61 (receiver)
1
Relay output
2
Relay output
3
Voltage supply
When connecting to a PLC, the min. switching capacity of the relay
must be taken into account.
If ncecssary, a correspondingly dimensioned resistor must be
connected in parallel to the PLC input. With a voltage U
B
von 24 V and
a PLC inner resistance R
i
>
100 kΩ, the additional load resistance R
L
must be between 6.8 and 8.2 kΩ.
Wiring plan
Connection to a PLC
VEGAMIP R
61 • - Relay
25
5 Connecting to power supply
35786
-
EN
-120228