6 Set up with the indicating and adjustment module

VEGAPULS 66 enamel • Profibus PA

36529-EN-121011

The "Echo curve" shows the signal strength of the echoes over the

measuring range in dB. The signal strength enables an evaluation of

the quality of the measurement.

The "False signal suppression" displays the saved false echoes (see

menu "Additional settings") of the empty vessel with signal strength in

"dB" over the measuring range.

A comparison of echo curve and false signal suppression allows a

more accurate conclusion on measurement reliability. The selected

curve is continuously updated. With the [OK] key, a submenu with

zoom functions is opened:

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Agitators

Buildup or welded joints on vessel walls

Note:

A false signal suppression detects, marks and saves these false sig-

nals so that they are no longer taken into account for level measure-

ment.
This should be done with the low level so that all potential interfering

reflections can be detected.
Proceed as follows:
1. Select the menu item "Additional settins" with [->] and confirm

with [OK]. With [->] you have to select the menu item "False

signal suppression" and confirm with [OK].

Diagnoses/Curve indica-

tion

Additional adjustments/

False signal suppression