VEGA VEGAPULS 66 (≥ 2.0.0 - ≥ 4.0.0) enamel Profibus PA User Manual
Page 59
59
11 Supplement
VEGAPULS 66 enamel • Profibus PA
36529-EN-121011
3
4
2
1
Fig. 47: Data of the input variable
1 Reference plane
2 Measured variable, max. measuring range
3 Antenna length
4 Useful measuring range
Max. measuring range
35 m (114.83 ft)
Recommended measuring range
up to 35 m (114.83 ft)
Output variable
Output signal
digital output signal, format according to IEEE-754
Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ 1. FB
PV
Ʋ 2. FB
SV 1
Ʋ 3. FB
SV 2
Current value
Ʋ Non-Ex and Ex ia instrument
10 mA, ±0.5 mA
Ʋ Ex-d instruments
16 mA, ±0.5 mA
Resolution, digital
< 1 mm (0.039 in)
Accuracy (according to DIN EN 60770-1)
Process reference conditions according to DIN EN 61298-1
Ʋ Temperature
+18 … +30 °C (+64 … +86 °F)
Ʋ Relative humidity
45 … 75 %
Ʋ Air pressure
860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Installation reference conditions