8 Maintenance and fault rectification

VEGABAR 67 • Foundation Fieldbus - climate compensated

39446-EN-130321

F

T

: Temperature coefficient (influence of medium or ambient

temperature)

F

Kl

: Deviation

Level measurement 1.5 mWs
Ambient temperature 40 °C, product temperature 10 °C
VEGABAR 67 with measuring range 0.2 bar
Deviation < 0.1 %
Calculation of the set Turn Down:
TD = 200 mbar/147 mbar, TD = 1.4
Basic accuracy digital output signal in percent:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.15 + 0.4 x TD) %

F

Kl

= 0.1 %

F

perf

= √((0.15 % + 0.4 % x 1.4)

2

+ (0.1 %)

2

)

F

perf

= 0.72 %

Total deviation digital output signal in percent:

F

total

= F

perf

+ F

stab

F

stab

= (1 % x 1.4)/year

F

stab

= 1.4 %

F

total

= 0.72 % + 1.4 % = 2.12 %

Total deviation digital output signal absolute:

F

total

= 2.12 % x 147 mbar/100 % = 3.11 mbar = 31.77 mm

8.4 Exchanging the electronics module

In case of a defect, the electronics module can be exchanged by the

user against an identical type. If no electronics module is available on

side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial

number. The electronics module with serial number includes order-

specific data such as factory setting, seal material etc. These are not

included in the electronics module without serial number.
The serial number is stated on the type label of VEGABAR 67 or on

the delivery note.

8.5 Software update

The software version of VEGABAR 67 can be determined as follows:

on the type label of the electronics

Via the display and adjustment module

via PACTware

You can view all software histories on our website www.vega.com.

Make use of this advantage and get registered for update information

via e-mail.

Example

Advertising