VEGA VEGABAR 67 Foundation Fieldbus - climate compensated User Manual

Page 56

Advertising
background image

56

10 Supplement

VEGABAR 67 • Foundation Fieldbus - climate compensated

39446-EN-130321

Spring-loaded terminals for wire cross-

section up to

2.5 mm² (AWG 14)

Connection cable between IP 68 instrument and external housing:

Ʋ Configuration

four wires, one suspension wire, one breather capillary,

screen braiding, metal foil, mantle

Ʋ Wire cross-section

0.5 mm² (AWG 20)

Ʋ Wire resistance

< 0.036 Ω/m (0.011 Ω/ft)

Ʋ Standard length

5 m (16.4 ft)

Ʋ Max. length non-Ex

250 m (820.21 ft)

Ʋ Max. length Ex

180 m (591.55 ft)

Ʋ Min. bending radius at 25 °C/77 °F

25 mm (0.985 in)

Ʋ Diameter

approx. 8 mm (0.315 in)

Ʋ Cable extraction force

19)

≥ 650 N (146.1 lbf)

Ʋ Colour - standard PE

Black

Ʋ Colour - standard PUR

Blue

Ʋ Colour - Ex-version

Blue

Display and adjustment module
Voltage supply and data transmission

through the sensor

Indication

LC display in dot matrix

Adjustment elements

4 keys

Protection rating

Ʋ unassembled

IP 20

Ʋ mounted into the sensor without cover IP 40

Material

Ʋ Housing

ABS

Ʋ Inspection window

Polyester foil

Voltage supply
Operating voltage

Ʋ Non-Ex instrument

9 … 32 V DC

Ʋ Ex ia instrument

9 … 24 V DC

Ʋ Ex d instrument

9 … 32 V DC

Operating voltage with illuminated display and adjustment module

Ʋ Non-Ex instrument

12 … 32 V DC

Ʋ Ex-ia instrument

12 … 24 V DC

Ex d instrument

12 … 32 V DC

Power supply by/max. number of sensors

Ʋ H1 power supply

max. 32 (max. 10 with Ex)

Electrical protective measures
Protection rating

19)

With this extraction force, the suspension cable can be extracted out of the transmitter.

Advertising