VEGA VEGABAR 54 4 … 20 mA_HART User Manual

Page 33

Advertising
background image

33

6 Set up with the display and adjustment module PLICSCOM

VEGABAR 54 • 4 … 20 mA/HART

36726-EN-130321

Unit
Unit of measurement
bar

Temperature unit
°C

3. Activate the selection with [OK] and select "Units of measure-

ment with [->].

4. Activate the selection with [OK] and select the requested unit with

[->] (in the example mbar).

5. Confirm with [OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to mbar.
Proceed as follows to select the temperature unit:

5)

1. Activate the selection with [OK] and select "Temperature unit

with [->].

2. Activate the selection with [OK] and select the requested unit with

[->] (e.g. °F).

3. Confirm with [OK].
The temperature unit is hence switched over from °C to °F.

Proceed as follows:
1. Activate in the menu item "Position correction" the selection with

[OK].

Position correction
Offset

P

=
+0000 mbar
53 mbar

2. Select with [->], e.g. to accept actual measured value.

Position correction
Accept current measured

value?

Accept
Edit

3. Confirm with [OK] and move to min.(zero) adjustment with [->].

Proceed as follows:
1. Edit the mbar value in the menu item "zero" with [OK].

Zero
000.0 %

P

=
+0000.0 mbar

0000.0 mbar

2. Set the requested mbar value with [+] and [->].
3. Confirm with [+] and move to span adjustment with [->].
The zero adjustment is finished.

Carry out a position cor-

rection

Carrying out zero adjust-

ment

5)

Selection options: °C, °F.

Advertising