6 Set up with the display and adjustment module PLICSCOM

VEGABAR 54 • 4 … 20 mA/HART

36726-EN-130321

SIL

HART mode

6)

PIN

Application

Copy sensor data

Copy sensor data?

A linearisation is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. in a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearisation curves are preprogrammed for

these vessels. They represent the correlation between the level per-

centage and vessel volume. By activating the appropriate curve, the

volume percentage of the vessel is displayed correctly. If the volume

should not be displayed in percent but e.g. in l or kg, a scaling can be

also set in the menu item "Display".

Linearization curve

Linear

Enter the requested parameters via the appropriate keys, save your

settings and jump to the next menu item with the [->] key.
Basic adjustment

The reset function resets all parameters adjusted by the user to the

delivery status and the peak values to the actual values.

Reset

Select reset?

Reset
Basic adjustment
Peak value, measured value
Peak value, temperature

Basic adjustment

The "Reset" "Basic adjustment" resets the values of the following

menu items:

Menu section

Function

Reset value

Basic settings

Zero/Min. adjustment

Measuring range begin

Span/Max. adjustment

Measuring range end

Density

1 kg/l

Density unit

kg/l

Linearization curve

Reset

6)

With instruments with signal output 4 … 20 mA/HART