8 Maintenance and fault rectification

8.1 Maintenance

When the instrument is used properly, no special maintenance is
required in normal operation.

8.2 Rectify malfunctions

The operator of the system is responsible for taking suitable measures
to remove interferences.

VEGAFLEX

66 offers a maximum of reliability is ensured. Never-

theless, faults can occur during operation. These may be caused by
the following, e.g.:

l

Sensor

l

Process

l

Voltage supply

l

Signal processing

The first measures to be taken are to check the output signals as well
as to evaluate the error messages via the indicating and adjustment
module. The procedure is described below. Further comprehensive
diagnostics can be carried out on a PC with the software PACTware
and the suitable DTM. In many cases, the causes can be determined
this way and faults rectified.

However, should these measures not be successful, call the VEGA
service hotline in urgent cases under the phone no. +49 1805 858550.

The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.

The following table describes possible errors and helps to remove
them:

Error

Cause

Removal

When an additio-
nal instrument is
connected, the
segment fails.

Max. supply cur-
rent of the seg-
ment coupler
exceeded

Measure the current consumption,
reduce size of segment

Reaction when malfunc-
tions occur

Causes of malfunction

Fault rectification

24 hour service hotline

Checking Profibus PA

VEGAFLEX

66 • Profibus PA