6 Set up with the indicating and adjustment module

VEGAPULS 61 • Foundation Fieldbus

36502-EN-121011

ing the product level. These settings can be made ahead of time

without the instrument having to be installed.

Proceed as follows:
1. Select with [->] the menu item max. adjustment and confirm with

[OK].

2. Prepare the percentage value for editing with [OK] and set the

cursor to the requested position with [->].

3. Set the requested percentage value with [+] and save with [OK].

The cursor jumps now to the distance value.

4. Enter the appropriate distance value in m (corresponding to the

percentage value) for the full vessel. Keep in mind that the max.

level must lie below the min. distance to the antenna edge.

5. Save settings with [OK]

The respective min. and max. measured value is saved in the sensor.

The values are displayed in the menu item "Peak values".

When non-contact level sensors are used, the measurement can be

influenced by the respective process conditions. In this menu item,

the measurement reliability of the level echo is displayed as dB value.

The measurement reliability equals signal strength minus noise. The

higher the value, the more reliable the measurement. With a function-

ing measurement, the values are > 10 dB.

The "Echo curve" shows the signal strength of the echoes over the

measuring range in dB. The signal strength enables an evaluation of

the quality of the measurement.

Setup/Max. adjustment

Diagnosis/Peak value

Diagnosis/Measurement

reliability

Diagnoses/Curve indica-

tion