2 parameter list – VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 73

Advertising
background image

73

11 Supplement

VEGAPULS 61 • Foundation Fieldbus

36502-EN-121011

The following algorithms are available:

Flow compensation, linear

Flow compensation, square root

Flow compensation, approximate

BTU flow

Traditional Multiply Divide

Average

Traditional Summer

Fourth order polynomial

Simple HTG compensated level

Fourth order Polynomial Based on PV

Fig. 65: Schematic presentation function block Arithmetic

11.2 Parameter list

The following table gives you an overview of the parameters used.

FF desciptor

Description

Unit

PRIMARY_VALUE

PRIMARY_VALUE (Linearized value). This is the process val-

ue after min/max adjustment and Linearization with the status

of the transducer block. The unit is defined in "PRIMARY_VAL-

UE_UNIT"

PRIMARY_VALUE_UNIT

Selected unit code for "PRIMARY_VALUE"

SECONDARY_VALUE_1

This is the measured value after min/max adjustment with the

status of the transducer block. The unit is defined in "SECOND-

ARY_VALUE_1_UNIT"

SECONDARY_VALUE_1_

UNIT

Selected unit code for "SECONDARY_VALUE_1"

SECONDARY_VALUE_2

This is the distance value ("sensor_value") with the status of the

transducer block. The unit is defined in "SECONDARY_VAL-

UE_2_UNIT"

FILL_HEIGHT_VALUE

Filling height. The unit is defined in "FILL_HEIGHT_VALUE_

UNIT"

FILL_HEIGHT_VALUE_UNIT Filling height unit
CONST_VALUE

Constant value