VEGA VEGAPULS 61 (≥ 2.0.0 - ≥ 4.0.0) Foundation Fieldbus User Manual

Page 43

Advertising
background image

43

6 Set up with the indicating and adjustment module

VEGAPULS 61 • Foundation Fieldbus

36502-EN-121011

The "False signal suppression" displays the saved false echoes (see

menu "Additional settings") of the empty vessel with signal strength in

"dB" over the measuring range.

A comparison of echo curve and false signal suppression allows a

more accurate conclusion on measurement reliability. The selected

curve is continuously updated. With the [OK] key, a submenu with

zoom functions is opened:

"X-Zoom": Zoom function for the meas. distance

"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"

"Unzoom": Reset the presentation to the nominal measuring range

with single magnification

With the function "Echo curve memory" the echo curve can be saved

at the time of setup. This is generally recommended; for using the As-

set Management functions it is absolutely necessary. If possible, the

curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolu-

tion echo curve can be displayed and used to recognize signal

changes over the operating time. In addition, the echo curve of the

setup can be also displayed in the echo curve window and compared

with the actual echo curve.

The following circumstances cause interfering reflections and can

influence the measurement:

High sockets

Vessel installations such as struts

Agitators

Buildup or welded joints on vessel walls

Diagnostics/Echo curve

memory

Additional adjustments/

False signal suppression