3 exchanging the electronics module – VEGA VEGAFLEX 66 (-200…+400°C) Foundation Fieldbus User Manual

Page 39

Advertising
background image

Error

Cause

Removal

Measured value
on the indicating
and adjustment
module does not
correspond to the
value in the PLC

The menu item
"

Display - Dis-

play value

"

is

not set to "

AI-

Out

"

Check values and correct, if neces-
sary

Instrument does
not appear during
connection setup

Profibus DP cab-
le pole-reversed

Check cable and correct, if necessary

Incorrect termina-
tion

Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification

Instrument not
connected to the
segment

Check and correct, if necessary

In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.

Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.

8

.3 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.

In Ex applications only one instrument and one electronics module with
respective Ex approval may be used.

If there is no electronics module available on site, one can be ordered
from the VEGA agency serving you.

The new electronics module must be loaded with the settings of the
sensor. These are the options:

l

At the factory by VEGA

l

Or on site by the user

In both cases, the sensor serial number is necessary. The serial
numbers are stated on the type label of the instrument, inside the
housing or on the delivery note.

Information:
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Oscillator").

Reaction after fault rec-
tification

Sensor serial number

VEGAFLEX

66 • Foundation Fieldbus

39

8 Maintenance and fault rectification

34176

-

EN

-100426

Advertising