VEGA VEGABAR 67 Foundation Fieldbus User Manual

Page 53

Advertising
background image

53

10 Supplement

VEGABAR 67 • Foundation Fieldbus

36744-EN-130321

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

0 … 25 bar/0 … 2500 kPa

130 bar/13000 kPa

0 bar abs.

Nominal measuring ranges and overload capability in psig
The specifications are only an overview and refer to the measuring cell. Limitations due to the ma-

terial and version of the process fitting are possible. The specifications on the nameplate apply.

Nominal range

Overload capacity, max.

pressure

Overload capacity, min. pres-

sure

Gauge pressure
0 … +1.5 psig

+200 psig

-15 psig

0 … +3 psig

+290 psig

-15 psig

0 … +6 psig

+430 psig

-15 psig

0 … +15 psig

+500 psig

-15 psig

0 … +35 psig

+700 psig

-15 psig

0 … +70 psig

+950 psig

-15 psig

0 … +150 psig

+1300 psig

-15 psig

0 … +350 psig

+1900 psig

-15 psig

0 … +900 psig

+2900 psig

-15 psig

Absolute pressure
0 … 15 psi

500 psi

0 psi

0 … 35 psi

700 psi

0 psi

0 … 70 psi

900 psi

0 psi

0 … 150 psi

1300 psi

0 psi

0 … 350 psi

1900 psi

0 psi

Reference conditions and actuating variables (according to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1

Ʋ Temperature

18 … 30 °C (64 … 86 °F)

Ʋ Relative humidity

45 … 75 %

Ʋ Air pressure

860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)

Determination of characteristics

limit point adjustment according to DIN 16086

Characterstic curve

Linear

Reference installation position

upright, diaphragm points downward

Influence of the installation position

< 5 mbar/0.5 kPa (0.07 psig)

Deviation determined according to the limit point method according to IEC 60770

12)

Applies to the digital signal output (HART, Profibus PA, Foundation Fieldbus) as well as to ana-

logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal

measuring range/set span.
Deviation

12)

Incl. non-linearity, hysteresis and non-repeatability.

Advertising