7 Diagnosis, Asset Management and service

VEGAPULS WL 61 • Profibus PA

38062-EN-121011

The following table shows the codes and text messages in the status

message "Failure" and gives information on the reason and rectifica-

tion. Keep in mind that some specification are only valid for four-wire

instruments and the electronics with VEGAPULS WL 61 cannot be

exchanged by the user.

Code
Text mes-

sage

Cause

Rectification

PA DevS-

pec
Diagnosis

F013
no meas-

ured value

available

– Sensor does not

detect an echo during

operation

– Antenna system con-

taminated or defective

– Check or correct

installation and/or

parameter adjustment

– Clean or exchange

process component or

antenna

Bit 0

F017
Adjustment

span too

small

– Adjustment not within

specification

– Change adjustment

according to the limit

values (difference

between min. and

max. ≥ 10 mm)

Bit 1

F025
Error in the

lineariza-

tion table

– Index markers are not

continuously rising, for

examle unlogical value

pairs

– Check linearization

table

– Delete table/Create

new

Bit 2

F036
No op-

erable

software

– Failed or interrupted

software update

– Repeat software

update

– Check electronics

version

– Exchanging the elec-

tronics

– Send instrument for

repair

Bit 3

F040
Error in the

electronics

– Hardware defect

– Exchanging the elec-

tronics

– Send instrument for

repair

Bit 4

F080

– General software error

– Separate operating

voltage briefly

Bit 5

F105
Determine

measured

value

– The instrument is still

in the start phase, the

measured value could

not yet be determined

– Wait for the warm-up

phase

– Duration depending

on the version and

parameter adjustment

up to approximately

3 min.

Bit 6

F113
Communi-

cation error

– Error in the internal

instrument communi-

cation

– Separate operating

voltage briefly

– Send instrument for

repair

Bit 7

Failure (failure)