4 measurement error during filling – VEGA VEGAPULS WL 61 Profibus PA User Manual

Page 32

Advertising
background image

32

7 Diagnosis, Asset Management and service

VEGAPULS WL 61 • Profibus PA

38062-EN-121011

Fault description

Error pattern

Cause

Rectification

3. Measured value

jumps towards 100 %

Level

time

0

– Due to the process, the ampli-

tude of the product echo sinks

– A false signal suppression was

not carried out

– Carry out false signal suppres-

sion

– Amplitude or position of a

false echo has changed (e.g.

condensation, buildup); false

signal suppression no longer

matches

– Determine the reason for the

changed false echo, carry out

false signal suppression, e.g.

with condensation

7.4 Measurement error during filling

Fault description

Error pattern

Cause

Rectification

4. Measured value re-

mains unchanged

during filling

Level

time

0

– False echoes in the close range

too big or product echo too

small

– Strong foam or spout genera-

tion

– Max. adjustment not correct

– Eliminate false echoes in the

close range

– Check measurement situation:

Antenna must protrude out of

the socket, installations

– Remove contamination on the

antenna

– Minimize interfering instal-

lations in the close range by

changing the polarization

direction

– Create a new false signal sup-

pression

– Adapt max. adjustment

5. Measured value re-

mains in the bottom

section during filling

Level

time

0

– Echo from the tank bottom

larger than the product echo,

for example, with products with

ε

r

< 2.5 oil-based, solvents

– Check application parameters

Medium, Vessel height and

Floor form, adapt if necessary

6. Measured value re-

mains momentarily

unchanged during fill-

ing and then jumps to

the correct level

Level

time

0

– Turbulence on the product

surface, quick filling

– Check application parameters,

change if necessary, e.g. in

dosing vessel, reactor

7. Measured value

jumps towards 0 %

during filling

Level

time

0

– Amplitude of a multiple echo

(vessel top - product surface) is

larger than the level echo

– Check parameter "Application",

especially vessel top, product

type, dished end, high dielectric

figure, adapt if necessary

– The level echo cannot be distin-

guished from the false echo at

a false echo position (jumps to

multiple echo)

– Remove/reduce false echo:

minimize interfering installa-

tions by changing the polariza-

tion direction

– Chose a more suitable installa-

tion position

8. Measured value

jumps towards 100 %

during filling

Level

time

0

– Due to strong turbulence and

foam generation during filling,

the amplitude of the product

echo sinks. Measured value

jumps to the false echo

– Carry out false signal suppres-

sion