5 connecting to power supply, 1 preparing the connection – VEGA VEGABAR 86 4 … 20 mA_HART - Operating Instructions User Manual

Page 18

Advertising
background image

18

5 Connecting to power supply

VEGABAR 86 • 4 … 20 mA/HART

45039-EN-131010

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

If overvoltage surges are expected, overvoltage arresters should

be installed

Power supply and current signal are carried on the same two-wire

cable. The operating voltage can differ depending on the instrument

version.
The data for power supply are specified in chapter "Technical data".
Provide a reliable separation between the supply circuit and the

mains circuits according to DIN EN 61140 VDE 0140-1.
Keep in mind the following additional factors that influence the operat-

ing voltage:

Lower output voltage of the power supply unit under nominal load

(e.g. with a sensor current of 20.5 mA or 22 mA in case of fault

message)

Influence of additional instruments in the circuit (see load values in

chapter "Technical data")

The instrument is connected with standard two-wire cable without

screen. If electromagnetic interference is expected which is above the

test values of EN 61326-1 for industrial areas, screened cable should

be used.
Use cable with round cross section for instruments with housing and

cable gland. To ensure the seal effect of the cable gland (IP protection

rating), find out which cable outer diameter the cable gland is suitable

for.

5 … 9 mm (0.20 … 0.35 in)

6 … 12 mm (0.24 … 0.47 in)

10 … 14 mm (0.40 … 0.55 in)

Use a cable gland fitting the cable diameter.
We generally recommend the use of screened cable for HART multi-

drop mode.

With plastic housing, the NPT cable gland or the Conduit steel tube

must be screwed without grease into the threaded insert.
Max. torque for all housings see chapter "Technical data".

If screened cable is required, we recommend connecting the cable

screen on both ends to ground potential. In the sensor, the screen

must be connected directly to the internal ground terminal. The

ground terminal on the outside of the housing must be connected to

the ground potential (low impedance).

With Ex systems it must be ensured that the grounding corresponds

to the installation regulations.

Safety instructions

Voltage supply

Connection cable

Cable gland ½ NPT

Cable screening and

grounding

Advertising