VEGA VEGABAR 86 4 … 20 mA_HART - Operating Instructions User Manual

Page 41

Advertising
background image

41

6 Set up with the display and adjustment module

VEGABAR 86 • 4 … 20 mA/HART

45039-EN-131010

With a reset, certain parameter adjustments carried out by the user

are reset.

The following reset functions are available:
Delivery status: Restoring the parameter settings at the time of

shipment from the factory incl. the order-specific settings. A user-pro-

grammable linearization curve as well as the measured value memory

will be deleted.
Basic settings: Resetting the parameter settings incl. special

parameters to the default values of the respective instrument. A pro-

grammed linearization curve as well as the measured value memory

is deleted.
The following table shows the default values of the instrument. De-

pending on the instrument version or application, all menu items may

not be available or some may be differently assigned:

Reset - Setup

Menu item

Parameter

Default value

Measurement

loop name

Sensor

Application

Application pro-

cess pressure
Application level

No reset

Slave for elec-

tronic differential

pressure

No reset

Units

Unit of measure-

ment

mbar (with nominal measuring range

≤400 mbar)
bar (with nominal measuring rang-

es ≥1 bar)

Temperature unit °C

Position correc-

tion

0.00 bar

Adjustment

Zero/Min. adjust-

ment

0.00 bar
0.00 %

Span/Max. adjust-

ment

Nominal measuring range in bar
100.00 %

Damping

Integration time

0.0 s

Additional adjustments

- Reset

Advertising